System 2500 Operating & Installation Manual - Revision 075-2
3) Verify that 6 pin plug-in terminal strip is securely installed into header
(receptacle) on Logic Unit.
4) Notify factory.
040 PROCESSOR INTERNAL DATA ERROR
1) Notify factory.
041 LOSS OF RESOLVER SIGNAL
1) Verify that resolver cable round connector is securely installed to its mate on
rear of resolver package.
2) Verify that resolver cable is properly wired to 6-pin plug-in terminal strip for
Logic Unit.
3) Verify that 6-pin plug-in terminal strip is securely installed into header
(receptacle) on Logic Unit.
4) Notify factory.
042 PROCESSOR INTERNAL DATA ERROR
1) Notify factory.
043 PROCESSOR ERROR
1) Notify factory.
044 PROCESSOR ERROR
1) Notify factory.
045 RESOLVER SPEED EXCEEDED MAXIMUM LIMIT FOR SYSTEM 2500
1) System 2500 is designed for a maximum speed of 2000 strokes per minute. If
the system is being used on a high speed machine, check to be sure that this limit
is not being exceeded.
2) Verify that resolver cable round connector is securely installed to its mate on
rear of resolver package.