April 17, 2000 Man ual Revisio n 1.0
4.14
monitor and press the RESET ERROR softkey. If the error message does not
return, connect the strain gauges one at a time to determine which gauge causes
the shorted condition or verify that the resistance of each gauge (Vref to Gnd) is
approximately 350 ohms. If the problem remains, it indicates a failure on the
tonnage monitor analog board.
Section 4.4.3 Resetting Errors
If an alarm or error condition is detected, a stop signal is provided to the press control and a RESET
ERROR softkey provided in the Main Tonnage Monitor screen. If configured to lock out access to
resetting errors, this softkey will appear only with the RUN/PROG keyed selector switch in the PROG
position. In addition, if access codes have been enabled (see Section 2 for details), the operator will also
require an access code to reset the tonnage monitor.